| Plan Review Notes For Permit 04081100 |
| Permit Number |
04081100 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-09-22 00:00:00 | DENIED | | | REFERENCE: FBC-2001 424 SWIMMING POOLS | | | | | | 1) SHT 2 EQUIPMENT SCHEDULE INDICATES 2 | | | VACUUM FITTINGS, BUT THE POOL PLAN SHOWS | | | 1 VACUUM FITTING. PLEASE CLAIRFY/CORREL- | | | ATE. SECTION 104.2.1 | | | 2) SHT 2 EQUIPMENT SECHEULE INDICATES A | | | STATIC FITTING, BUT THE POOL PLAN SHOWS | | | NO STATIC LINE. PLEASE CLAIRFY/CORRELATE | | | SECTION 104.2.1 | | | 3) SHTS 2 & 3 EQUIPMENT SCHEDULE SHOWS | | | 2 300 SF FILTERS, BUT EQUIPMENT ROOM | | | PLAN VIEW INDICATES 1. PLEASE CLAIRFY/ | | | CORRELATE. SECTION 104.2.1 | | | 4) WASTE FROM THE FILTER SHALL DRAIN IN- | | | TO THE SANITARY SYSTEM AND THE OVERFLOW | | | AND POOL DRAIN SHALL CONNECT TO THE | | | STORM SYSTEM. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|