Plan Review Notes
Plan Review Notes For Permit 04081070
Permit Number 04081070
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2004-08-26 00:00:00***********DENIED***********************
 1) NEW FIRE ALARM SYSTEMS SHALL BE UL
 LISTED FOR CENTRAL STATION SERVICE.
  
 2) ALL NEW FIRE ALARM SYSTEMS THAT
 SUPERVISE FIRE SPRINKLER SYSTEMS SHALL
 BE UL CERTIFICATED AND HAVE DOCUMENT
 ATTESTING TO THIS CERTIFICATION PRIOR TO
 APPROVAL OF THESE PLANS.
  
 3) ALL DUCT DETECTORS SHALL SEND AND PUT
 THE SYSTEM IN GENERAL FIRE ALARM MODE IN
 THE CITY OF WEST PALM BEACH NOT A
 SUPERVISORY SIGNAL.
  
 4) THE FIRE ALARM SYSTEM SHALL BE CLASS
 "A" OR FULLY ADDRESSABLE.
  
 5) WHEN THE FIRE ALARM CONTROL UNIT
 INCLUDING THE DIALER-COMMUNICATOR, IS
 REPLACED IN AN EXISTING SYSTEM, IT WILL
 BE TREATED AS IF IT WERE A NEW SYSTEM.
  
 NATE MCCRAY, CAPTAIN
 561-835-2910 OR 561-805-6722