| Plan Review Notes For Permit 04081064 |
| Permit Number |
04081064 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-09-15 00:00:00 | DENIED; | | | PLUMBING RISER; | | | 1.WASHER DISCHARGE TO BE 2". | | | 2.W/C'S HAVE A TRAP BUILT INTO THE BOWL | | | DON'T SHOW TRAP ON RISER DIAGRAM. | | | 3.2" VENT THRU ROOF IS NOT REQUIRED IN | | | KITCHEN M/V IS OK. | | | 4.W/M TO DISCHARGE DOWN STREAM OF | | | MASTER BATH. SEC. 909.1 | | | SEE RISER DIAGRAM MARKED IN RED. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|