| 2004-08-25 00:00:00 | ************ UNSAT ************* |
| | |
| | 1)NOTE: PLEASE SEE 210.52 FOR SOME |
| | MISSING RECEPTS. PLEASE SEE PLANS. |
| | |
| | 2)NOTE: PLEASE SEE 210.52D FOR MISSING |
| | GFI W/IN 3' OF SINK IN BATH RM. |
| | PLEASE SEE PLANS |
| | |
| | 3)NOTE: PLEASE SEE 210.70 AND LS 101 5-8 |
| | FOR MEANS OF EGRESS LIGHTING REQUIRED. |
| | PLEASE SEE REDLINED LOCATIONS. |
| | |
| | 4) NOTE: PLEASE LIST ALL THE REQ'D |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3 |
| | |
| | 5 ) NOTE: PLEASE SEE MISSING RECEPTS FOR |
| | FRONT AND/OR REAR OF DWELLING. |
| | 210.52E |
| | MISSING FRONT. |
| | |
| | 6 )NOTE: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | 210.12 2002 NEC |
| | |
| | 7)NOTE: PLEASE SEE LAUNDRY/WASHER SHOWN |
| | AT 1.2 KW, A MIN OF 1.5 REQUIRED PER |
| | 220.16, 220.31 |
| | |
| | 8)NOTE: PLEASE SEE 250.50 FOR MISSING |
| | FOOTER STEEL REQUIRED AS PART OF THE |
| | GROUNDING ELECTRODE SYSTEM. |
| | |
| | 9)NOTE: PLEASE SEE MISSING EQUIPMENT |
| | GROUNDING FROM PANEL TO AHU/CU. |
| | 250.110,250.122 |
| | |
| | 10)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | |
| | **PLEASE SEE ONE BEDRM** |
| | |
| | 11)NOTE: PLEASE PROVIDE ROOM DESIGNATION |
| | ON PLANS. |
| | |
| | **PLEASE SEE ONE SET OF PLANS HAS MOST |
| | OF THE ABOVE ITEMS REDLINED AT LOCATIONS |
| | OF MENTION. |
| | |
| | **PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| | AND ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |