| 2004-10-27 00:00:00 | ********* UNSAT 2ND REVIEW ********* |
| | |
| | PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW STILL NEED TO BE ADDRESSED. |
| | |
| | 1)NOTE: NOTE #1 OK. |
| | |
| | 2)NOTE: NOTE #2 OK. |
| | |
| | 3)NOTE: NOTE #3 NO, PLEASE SEE NO SPECS |
| | FOR GENERATOR, ATS, OR UPS WAS SUBMITTED |
| | BACK WITH PACKAGE.? |
| | PLEASE SUBMITMANUFACTURER SPECS FOR |
| | THE ABOVE ITEMS AT THIS TIME. |
| | IF THESE ITEMS ARE NOT SUBMITTED AT THIS |
| | TIME, ALL OF THESE ITEMS WILL BE REQUIR- |
| | -ED TO BE SUBMITTED UNDER SEPARATE |
| | PERMIT. ADDITIONAL FEES WILL BE ASSESSED |
| | AT THAT TIME. |
| | |
| | 4)NOTE: NOTE #4 NO, PLEASE SHOW GROUND- |
| | -ING OF GENERATOR. ATS IS SHOWN AS A 3- |
| | -POLE UNIT, THIS WOULD NOT BE SEPARATE- |
| | -LYDERIVED SYSTEM. |
| | **PLEASE ALSO KEEP IN MIND, IF NEUTRAL |
| | IS NOT BROKEN, THEN ANY UNBALANCED LOAD |
| | MY FEED BACK TO FPL.*** |
| | 250.24,250.30,250.50 |
| | |
| | 5)NOTE: NOTE #5 NO, COULD NOT LOCATE |
| | ANY DEATIL FOR THIS. |
| | 110.27 ETC. |
| | |
| | 6)NOTE: NOTE #6 OK |
| | |
| | 7)NOTE: NOTE #7 OK. |
| | |
| | PLEASE SEE ATTACHED COPY OF FS 553.80(2) |
| | (B). THIS IS ONLY A NOTICE AT THIS TIME |
| | AND MUST BE GIVEN. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | INSERT NEW SHEETS INTO COMPLETET SETS |
| | FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SEE POSSIBLE COMMENTS FROM OTHER |
| | REVIEWERS WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | *** PLEASE SEE SOME PLANS STILL SHOW |
| | ADDRESS OF 700 S. ROSEMARY. *** |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |