| 2004-11-02 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04081018 |
| | ADD: 477 S ROSEMARY AV# 302 |
| | CONT: ANDERSON-MOORE |
| | TEL: (561)662-1819 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | 2NDREVIEW |
| | ACTION: DENIED |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT |
| | NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE |
| | FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 1)PROVIDE NOC RECORDED WITH THE CLERK |
| | OF |
| | COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2) COMMENT# 4 FROM THE PREVIOUS REVIEW, |
| | ENTRY DOORS SHALL COMPLY WITH SECTION |
| | 11-4.13.6MANUEVERING CLEARENCES AT |
| | DOORS |
| | SHEET A-1.0 DEMOLITION PLAN INDICATES |
| | THE ENTRY DOORS BEING CHANGED FROM |
| | INSWING TO OUT SWING DOORS. |
| | 11-4.13.6 MANEUVERING CLEARENCES |
| | AT DOORS. MINIMUM MANEUVERING |
| | CLEARENCES |
| | AT DOORS THAT ARE NOT AUTOMATIC OR |
| | POWER-ASSISTED SHALL BE AS SHOWN IN |
| | FIG. 25. THE FLOOR OR GROUND AREA WITH |
| | IN THE REQUIRED CLEARENCES SHALL BE |
| | CLEAR & LEVEL. |
| | |
| | 3) COMMENT# 5 FROM THE PREVIOUS REVIEW, |
| | SHEET A1-1 & A-3.1 PLATFORM: 403.2.4.1 |
| | PLATFORMS ARE TO BE MADE OF FIRE |
| | RETARDANT MATERIALS. TYPE II BUILDING |
| | SECTION 604, FLOORS ARE TO BE OF A NON- |
| | COMBUSTIBLE MATERIALS. |
| | |
| | 4) COMMENT# 7 FROM THE PREVIOUS REVIEW: |
| | 704.2.1.4 CORRIDOR PARTITIONS, SMOKE |
| | STOP PARTITIONS, HORIZONTAL EXIT PART- |
| | ITIONS, EXIT ENCLOSURES, AND FIRE |
| | RATED WALLS REQUIRED TO HAVE PROTECTED |
| | OPENINGS SHALL BE EFFECTIVELY AND |
| | PERMANETLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO |
| | THE |
| | AUTHORITY HAVING JURISDICTION. SUCH |
| | IDEN |
| | TIFICATION SHALL BE ABOVE ANY |
| | DECORATIVE |
| | CEILING CEILING AND IN CONCEALED |
| | SPACES. |
| | SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| | PROTECT ALL OPENINGS". |
| | |
| | 5) COMMENT# 8 FROM THE PREVIOUS REVIEW: |
| | 705.1.2 PENETRATIONS SHALL BE PRO- |
| | TECTED BY AN APPROVED PENETRATION FIRE- |
| | STOP SYSTEM AS TESTED IN ACCORDANCE |
| | WITH |
| | ASTM E 814, WITH A MINIMUM POSITIVE |
| | PRESSURE DIFFERENTIAL OF 0.01 INCH OF |
| | WATER COLUMN AND AN F RATING OF NOT |
| | LESS |
| | THAN REQUIRED RATING OF THE WALL |
| | PENETRATED. |
| | |
| | 6) PLANS (E-3) INDICATE A NEW TOWER, BUT |
| | |
| | THERE IS NO INFORMATION FOR A TOWER. |
| | IF TO BE COVERED UNDER THIS PERMIT, |
| | PRO- |
| | VIDE INFORMATION, LOCATION, HEIGHT, |
| | WIND |
| | INFORMATION, ETC. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |