2004-08-26 00:00:00************* UNSAT ****************
  
 1)NOTE: PLEASE SEE PLANS HAVE ADDRESS OF
 700 S ROSEMARY ALONG WITH PERMIT APPLI-
 -CATION.
 PLEASE SEE WORK APPEARS TO BE AT 477.
 PLEASE ALSO INCLUDE UNIT # TO BE.
  
 2)NOTE: PLEASE SEE 230.72, 230.76,230.79
 FOR MEANS OF DISC FROM GEN INTO SPACE.
 DISC MEANS MUST BE PLACED AT LOCATION OF
 NEW 400A MAIN FOR SPACE.
  
 3)NOTE: PLEASE SUBMIT SPECS FOR GEN/ATS
 UPS.
 PLEASE NOTE: EVEN IF ALL THIS EQUIPMENT
 IS OWNER SUPPLIED VALUE OF THESE ITEMS
 MUST BE INCLUDED IN VALUATION OF PERMIT.
 104.6.5 FBC.
  
 4)NOTE: PLEASE CLARIFY GROUNDING OF
 GENERATOR.IF SEP DERIVE OR NOT?
  
 5)NOTE: PLEASE PROVIDE INFORMATION ON
 HOW GENERATOR WILL BE FENCED/WALL OFF
 ETC.110.27
  
 5)NOTE: PLEASE SEE COMMENTS FROM OTHER
 REVIEWERS WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 6)NOTE: PLEASE REMOVE ALL OLD/VOIDED
 SHEETS AND INSERT NEW SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 7)NOTE: PLEASE SIGN PLANS WITH SIGNATURE
 FS 471.025
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  