| Date |
Text |
| 2004-09-16 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04081018 |
| | ADD:700 S ROSEMARY AV |
| | CONT: ANDERSON MOORE CONST |
| | TEL: (561)662-1819 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2)FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | DISCREPANCY, SHEET A-0 INDICATES WORK TO |
| | BE COMPLETED AT 700 S ROSEMARY, APPLICA- |
| | TION HAD 700 S ROSEMARY, SCRATCHED THRU |
| | AND 477 WAS ADDED. NOTE THE PCN IS STILL |
| | FOR 700 S ROSEMARY, CORRECT. ALSO ADD |
| | THE UNIT NUMBER WHERE WORK WILL BE COM- |
| | PLETED. |
| | |
| | 3) CHECK PROJECT INFORMATION IF THIS PRO |
| | JECT IS LOCATED AT 477 S ROSEMARY. |
| | CLASSIFICATION, EXITS, ETC |
| | |
| | 4) ENTRY DOORS SHALL COMPLY WITH SECTION |
| | 11-4.13.6 MANEUVERING CLEARENCES |
| | AT DOORS. MINIMUM MANEUVERING CLEARENCES |
| | AT DOORS THAT ARE NOT AUTOMATIC OR |
| | POWER-ASSISTED SHALL BE AS SHOWN IN |
| | FIG. 25. THE FLOOR OR GROUND AREA WITH |
| | IN THE REQUIRED CLEARENCES SHALL BE |
| | CLEAR & LEVEL. 18" MINIMUM PULL SIDE. |
| | IF EXISTING DOORS SHOW WHERE 20% OF |
| | WORK COMPLIES WITH DISPROPORTIONATE COST |
| | 11-4.1.6(2) DUTY TO PROVIDE AN |
| | ACCESSIBLE PATH OF TRAVEL TO ALTERED |
| | AREAS SHALL BE DEEMED DISPROPORTIONATE |
| | TO THE OVERALL ALTERATION WHEN THE COST |
| | EXCEEDS 20 % OF THE COST OF THE ALTERA- |
| | TION TO THE PRIMARY FUNCTION AREA. |
| | (A)(I) AN ACCESSIBLE ENTRANCE |
| | (II) AN ACCESSIBLE ROUTE |
| | (III) AT LEAST ONE ACCESSIBLE REST- |
| | ROOM FOR EACH SEX OR A SINGLE |
| | UNISEX RESTROOM |
| | (IIII) ACCESSIBLE TELEPHONE |
| | (IV) ELEMENTS SUCH AS PARKING, STOR- |
| | AGE OR ALARMS. |
| | |
| | 5) SHEET A1-1 PLATFORM: 403.2.4.1. PLAT- |
| | FORMS SHALL BE MADE OF FIRE RETARDANT |
| | TREATED MATERIALS. |
| | |
| | 6) SHEET A-3.1 TYPE II BUILDINGS REQUIRE |
| | BLOCKING IN WALLS TO BE NON-COMBUSTIBLE |
| | 609.2.1. |
| | |
| | 7)704.2.1.4 CORRIDOR PARTITIONS, SMOKE |
| | STOP PARTITIONS, HORIZONTAL EXIT PART- |
| | ITIONS, EXIT ENCLOSURES, AND FIRE |
| | RATED WALLS REQUIRED TO HAVE PROTECTED |
| | OPENINGS SHALL BE EFFECTIVELY AND |
| | PERMANETLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE |
| | AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| | TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| | CEILING CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| | PROTECT ALL OPENINGS". |
| | |
| | 8)705.1.2 PENETRATIONS SHALL BE PRO- |
| | TECTED BY AN APPROVED PENETRATION FIRE- |
| | STOP SYSTEM AS TESTED IN ACCORDANCE WITH |
| | ASTM E 814, WITH A MINIMUM POSITIVE |
| | PRESSURE DIFFERENTIAL OF 0.01 INCH OF |
| | WATER COLUMN AND AN F RATING OF NOT LESS |
| | THAN REQUIRED RATING OF THE WALL |
| | PENETRATED. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |