| Plan Review Notes For Permit 04080996 |
| Permit Number |
04080996 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-02-23 00:00:00 | ********** UNSAT 2ND REVIEW ********* | | | | | | PLEASE SEE THE SAME PLANS WERE SUBMITTED | | | BACK W/ OUT ANY CHANGES MADE. | | | | | | PLEASE SEE PREVIOUS REVIEW NOTES. | | | PLEASE ALSO SEE NOTES BELOW | | | | | | PLEASE SEE 424.3B FOR MIN OCP | | | FOR AHU @125%. | | | | | | PLEASE SEE BATH SHOWN AS 2-POLE | | | BRKR. | | | | | | PLEASE SEE MIN 2-SMALL | | | APPLIANCES PER 210.11C1,220.16 | | | | | | PLEASE SEE DISPOSAL AND FRIG ON | | | SAME CIRCUIT. PLEASE ALSO SEE KITCHEN | | | SINK DOES NOT INDICATE DISPOSAL RECEPT? | | | PLEASE SHOW AND CORRETC. | | | | | | | | | | | | PLEASE SEE ONE SET OF PLANS HAVE BEEN | | | REDLINED FOR AREAS OF NOTES. | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | INSERT NEW REVISED SHEETS INTO COMPLETE | | | SETS FOR REVIEW AND STAMPING. | | | ONE SET/COPY OF OLD SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | |
|