| 2004-08-27 00:00:00 | ************ UNSAT *************** |
| | |
| | 1)NOTE: PLEASE SEE PLANS ARE NOT |
| | COMPLETE AT THIS TIME. |
| | 210.52,210.70,215.5,220.31B,210.12 |
| | NFPA-72 8-1 |
| | |
| | 2)NOTE: PLEASE SEE FBC CHAPTER 34 FOR |
| | ADDITRIONS TO EXSITING DWELLINGS.. |
| | |
| | 3)NOTE: PLEASE CLARIFY IF A NEW A/C |
| | SYSTEM IS BEING ADDED FOR NEW ADDITION?? |
| | |
| | 4) NOTE: PLEASE SHOW OUTLET SPACING PER |
| | 210.52. 2',6`,12` RULE. |
| | |
| | 5 )NOTE: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | 210.12 |
| | |
| | 6)NOTE; SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | |
| | COMPLETE REVIEW CAN NOT BE DONE AT THIS |
| | TIME. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |