2004-08-27 00:00:00************ UNSAT ***************
  
 1)NOTE: PLEASE SEE PLANS ARE NOT
 COMPLETE AT THIS TIME.
 210.52,210.70,215.5,220.31B,210.12
 NFPA-72 8-1
  
 2)NOTE: PLEASE SEE FBC CHAPTER 34 FOR
 ADDITRIONS TO EXSITING DWELLINGS..
  
 3)NOTE: PLEASE CLARIFY IF A NEW A/C
 SYSTEM IS BEING ADDED FOR NEW ADDITION??
  
 4) NOTE: PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6`,12` RULE.
  
 5 )NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 210.12
  
 6)NOTE; SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
  
 COMPLETE REVIEW CAN NOT BE DONE AT THIS
 TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  