| Plan Review Notes For Permit 04080987 |
| Permit Number |
04080987 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-10-06 00:00:00 | ********PROVISO/REVISION ************* | | | | | | 1)NOTE: PLEASE SEE ELEVATOR DISCONNECT | | | IS STILL SHOWN AS 100A W/ A 150A FEED. | | | THIS DISCONNECT MUST BE RATED AT 150A'S | | | AND MAY HAVE THE 100A FUSES AS NOTED. | | | THIS HAS BEEN REDLINED ON PLANS. | | | PLEASE REVISE BEFORE ROUGH ELECTRICAL | | | INSPECTION. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|