| Date |
Text |
| 2004-08-28 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1) SHTS A1-1 & A1-2 SUBMIT A DETAIL FOR |
| | TOILET ROOMS SHOWING COMPLIANCE WITH |
| | SECTIONS 11-4.16, 11-4.19, & 11-4.22 & |
| | ALL SUBSECTIONS. SHOW MEASUREMENTS TO |
| | THE CENTER OF THE W/C OFF THE WALL AND |
| | THE CENTER OF LAV OFF WALL. SEE FIG 28 |
| | FOR THE W/C AND LAV MIN. 15" TO CENTER |
| | ON CLEAR FLOOR SPACE. |
| | 2) SHTS A1-1 & A1-2 SUBMIT A DETAIL FOR |
| | DRINKING FOUNTAINS SHOWING COMPLIANCE |
| | WITH SECTION 11-4.15. |
| | 3) COMMENT ADDRESSED ON PERMIT 04081108 |
| | 4) COMMENT ADDRESSED ON PERMIT 04081108 |
| | 5) SHT A2-2 DETAILS 04 & 08 SHOW HEIGHT |
| | AND WIDTH FOR SCUPPERS AND OVERFLOW |
| | SCUPPERS. SECTION 104.2.1 |
| | 6) SHT PO.1 GENERAL SPECIFICATIONS #24, |
| | AIR CHAMBERS ARE NOT APPROVED. DELETE |
| | REFERENCE. SECTION 604.9 |
| | 7) IN THE REMOVAL OF ANY PARY OF A |
| | DRAINAGE SYSTEM, DEAD ENDS SHALL BE PRO- |
| | HIBITED. SECTION 704.5 - ALL CAPPED PIP- |
| | ES SHALL BE CAPPED WITH A PERMINATE CAP |
| | 8) SHT P2.2 WATER RISER DIAGRAM, AIR |
| | CHAMBERS ARE NOT APPROVED. DELETE FROM |
| | THE RISER DIAGRAM. IS WATER HAMMER ARR- |
| | ESTORS ARE INSTALLED THEY SHALL BE LOCA- |
| | TED NEAR THE FIXTURE IN AN "EFFECTIVE |
| | RANGE" NOT IN THE CEILING. PDI-WH 201. |
| | 9) SHT P3.1 TANKLESS WATER HEATERS SHALL |
| | BE LISTED. SUBMIT MANUF. SPECIFICATIONS |
| | SECTION 303.4 |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |