Plan Review Notes
Plan Review Notes For Permit 04080912
Permit Number 04080912
Review Stop E
Sequence Number 1
Notes
Date Text
2004-08-24 00:00:00************* UNSAT **************
  
 1)NOTE: PLEASE CORRELATE PANELS/MCB
 FROM RISER AND PANELS .
 RISER SHOWS PANELS AS 150'S AND PANELS
 ARE SHOWN AS 200A'S.
 PLEASE ALSO SEE LOAD ON PANEL "A" IS
 SHOWN AT 149.16 W/ DERATING ALREADY
 TAKEN INTO ACCOUNT??
  
 2)NOTE: PLEASE SEE POOL PANEL LOAD
 SHOWN AT 10KW ON PANEL 'A'YET POOL PANEL
 SHOWS LOAD AT 6KW??
  
 3 )NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 PLEASE SEE 2002 210.12
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  