Plan Review Notes
Plan Review Notes For Permit 04080910
Permit Number 04080910
Review Stop E
Sequence Number 1
Notes
Date Text
2004-08-25 00:00:00******* UNSAT *********
  
 1)NOTE: PLEASE CORRELATE PANELS ON
 RISER AND PANELS. ONE SHOWS 150A PANELS
 AND OTHER SHOWS 200A PANELS.
 PLEASE ALSO SEE LOAD SHOWN AT 149.16
 EVEN AFTER DERATING HAS BEEN TAKEN??
  
 2)NOTE: PLEASE SEE LOAD SHOWN FOR POOL
 PANEL IS SHOWN AS 10KW ON PANEL "A" YET
 POOL PANEL DOES NOT INDICATE THIS LOAD.
  
 3 )NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 2002 NEC 210.12
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]