| Plan Review Notes For Permit 04080907 |
| Permit Number |
04080907 |
|
| Review Stop |
E |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2006-04-03 00:00:00 | *************UNSAT **************** | | | | | | 1)NOTE: PLEASE CORRELATE RISER DIAGRAM | | | WITH PANELS. | | | PLEASE SEE RISER SHOWS PANELS AS 200A | | | MCB AND PANELS ARE SHOWN AS 150A? | | | | | | 2) NOTE: PLEASE SEE RISER SHOWS PANEL | | | "A" FEEDING A POOL "DISCONNECT", HOWEVER | | | PLANS SEEM TOIN DICATE A POOL | | | "PANEL".? | | | PLEASE ALSO SEE THAT PANEL "A" DOES NOT | | | INDICATE A FEED TO EITHER A POOL | | | DISCONNECT OR POOL PANEL. | | | PLEASE CORRELATE AND AADJUST PLANS AND | | | RISER. | | | PLEASE SEE PLANS DO NOT INDICAT EITHER A | | | POOL PANEL OR A POOL DISCONNECT AT THE | | | LOCATION OF POOL EEQUIPMENT? | | | ** PLEASEBE SURE TO UPDATE LOAD | | | CALCULATIONS. | | | ** PLEASE ADJUST CONTINUOUS LOADS AT | | | 125%. (POOL PUMP). 215.3,230.42 | | | 215.5 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|