| Plan Review Notes For Permit 04080907 |
| Permit Number |
04080907 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2006-02-09 00:00:00 | ********* UNSAT ********** | | | | | | 1)NOTE: PLEASE SEE PLANS INDICATE AND | | | SHOW TWO COMPLETELT DIFFERENT RISER | | | DIAGRAMS. | | | IT IS UNCLEAR WHICH ONE IS FOR REVIEW. | | | IF THE RISER IS THE HANDRAWN ONE, PLEASE | | | CORRELATE WITH PLANS/ PANELS ETC. | | | IF HANDRAWN, WRONG SIZE GEC, FOR 400A | | | SERVICE BASED ON 250.66,310.15B6 | | | 1/0 MIN. | | | | | | 2)NOTE: PLEASE SEE MANY REQUIRED 20A | | | CIRCUITS ON PANEL "A" WHICH ARE SHOWN AS | | | 15A FOR SMALL APPL, DINING RM ETC. | | | 210.11C1,210.52B1 ETC | | | | | | 3)NOTE: PLEASE SEE MISSING RECEPT PER | | | 210.52 | | | | | | 4)NOTE: PLEASE SEE NO HANDWRITTEN | | | CHANGES OR WHITE-OUT PERMITTED ON PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | |
|