Plan Review Notes
Plan Review Notes For Permit 04080907
Permit Number 04080907
Review Stop E
Sequence Number 4
Notes
Date Text
2006-02-09 00:00:00********* UNSAT **********
  
 1)NOTE: PLEASE SEE PLANS INDICATE AND
 SHOW TWO COMPLETELT DIFFERENT RISER
 DIAGRAMS.
 IT IS UNCLEAR WHICH ONE IS FOR REVIEW.
 IF THE RISER IS THE HANDRAWN ONE, PLEASE
 CORRELATE WITH PLANS/ PANELS ETC.
 IF HANDRAWN, WRONG SIZE GEC, FOR 400A
 SERVICE BASED ON 250.66,310.15B6
 1/0 MIN.
  
 2)NOTE: PLEASE SEE MANY REQUIRED 20A
 CIRCUITS ON PANEL "A" WHICH ARE SHOWN AS
 15A FOR SMALL APPL, DINING RM ETC.
 210.11C1,210.52B1 ETC
  
 3)NOTE: PLEASE SEE MISSING RECEPT PER
 210.52
  
 4)NOTE: PLEASE SEE NO HANDWRITTEN
 CHANGES OR WHITE-OUT PERMITTED ON PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  