| Plan Review Notes For Permit 04080907 |
| Permit Number |
04080907 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-08-25 00:00:00 | ************ UNSAT **************** | | | | | | 1)NOTE: PLEASE CORRELATE PANELS. | | | RISER SHOWS 150A PANELS AND PANELS | | | INDICATE 200A PANELS? | | | PLEASE ALSO SEE PANELS INDICATE A 149.16 | | | A LOAD AFTER DERATING?? | | | | | | 2)NOTE: PLEASE SEE POOL PANEL LOAD | | | SHOWN AS 10KW ON PANEL 'A'. PLEASE | | | CORRELATE W/ POOL PANEL. | | | | | | 3 )NOTE: PLEASE LIST THE REQ'D ARC | | | FAULT PROTECTED CURCUIT(S) ON PANEL | | | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" | | | IN BEDROOMS ARE TO BE PROTECTED , | | | INCLUDING, LTS, RECEPTS, SD'S ETC. | | | 2002 NEC 210.12 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|