Plan Review Notes
Plan Review Notes For Permit 04080907
Permit Number 04080907
Review Stop E
Sequence Number 1
Notes
Date Text
2004-08-25 00:00:00************ UNSAT ****************
  
 1)NOTE: PLEASE CORRELATE PANELS.
 RISER SHOWS 150A PANELS AND PANELS
 INDICATE 200A PANELS?
 PLEASE ALSO SEE PANELS INDICATE A 149.16
 A LOAD AFTER DERATING??
  
 2)NOTE: PLEASE SEE POOL PANEL LOAD
 SHOWN AS 10KW ON PANEL 'A'. PLEASE
 CORRELATE W/ POOL PANEL.
  
 3 )NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 2002 NEC 210.12
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]