| 2005-08-24 00:00:00 | ******* UNSAT ******** |
| | |
| | PLEASE SEE SOME COMMENTS FROM PREVIOUS |
| | REVIEW AND NEW COMMENTS DUE TO CHANGES |
| | IN PLANS. |
| | |
| | |
| | |
| | 1)NOTE: PLEASE SEE THE CONDUCTORS FROM |
| | METER TO MAIN BRKR PANELS HAVE BEEN TO |
| | CORRECTED, HOWEVER PLEASE SEE "EQUIPMENT |
| | GROUNDING" CONDUCTOR ARE NOW SHOWN FROM |
| | METER TO MAIN/FIRST MEANS OF DISCONNECT. |
| | PLEASE SEE 250.6, AN 'EQUIP GROUNDING |
| | CONDUCTOR IS ONLY INSTALLED AFTER THE |
| | FIRST MEANS OF DISC. |
| | |
| | 2)NOTE: PLEASE SEE FEEDERS FOR POOL SUB |
| | PANEL ARE NOT SHOWN ON RISER DIAGRAM. |
| | PLEASE ALSO SEE PANEL DOES NOT INDICATE |
| | ANY LOAD FOR POOL PANEL?? |
| | PLEASE SEE THIS IS SHOWN AS "POOL DISC". |
| | PLEASE SEE POOL PANEL IS NOT SHOWN ON |
| | PLANS. |
| | 215.5, 310.16,240.4 ETC |
| | |
| | 3)NOTE: PLEASE SEE 250.66,310.15B6, THE |
| | MIN GROUNDING ELECTRODE CONDUCTOR SIZE |
| | IS 1/0, PLEASE SEE #2 SHOWN NEEDS TO BE |
| | CORRECTED. |
| | PLEASE SEE PREVIOUS PLANS AND ORIGINAL |
| | PLANS INDICATED A 300A SERVICE. PLEASE |
| | SEE SERVICE IS NOW BEING SHOWN AS |
| | 400A'S. THIS WAS NOT CORRECTED. |
| | |
| | 3)NOTE: PLEASE SEE PLANS DO NOT EITHER |
| | SHOW POOL HEATER AS INDICATED ON POOL |
| | PANEL OR 2ND CU AS INDICATED ON PANEL |
| | "A". |
| | PLEASE SEE PLANS, POOL EQUIPMENT IS |
| | SHOWN? OR IS THIS THE CU? |
| | PLEASE SEE MISSING DISC FOR A/C CU. |
| | 440.11PLEASE CORRELATE. |
| | |
| | 4)NOTE: PLEASE SEE A SPA TUB IS SHOWN ON |
| | PANEL SCHEDULE, HOWEVER THIS REQUIRED |
| | GFI PROTECTED OUTLET COULD NOT BE |
| | LOCATED ON PLANS. |
| | |
| | 5)NOTE: PLEASE SEE THIS IS A REVISION |
| | AND A REV FEE IS OWED. PLEASE SEE |
| | PREVIOUS REVISION FEE IS SHOWN AS NOT |
| | PAID.PLEASE SEE THAT ALL REV'S ARE |
| | PAID WHEN SUBMITTED. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |