| Plan Review Notes For Permit 04080905 |
| Permit Number |
04080905 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-08-17 00:00:00 | ******** UNSAT ******* | | | | | | 1)NOTE: PLEASE SEE 310.15B6 FOR MIN | | | CONDUCTORS FOR 200A PANELS. | | | | | | 2)NOTE: PLEASE SEE 250.66,310.15B6, THE | | | MIN GROUNDING ELECTRODE CONDUCTOR SIZE | | | IS 1/0, PLEASE SEE #2 SHOWN NEEDS TO BE | | | CORRECTED. | | | PLEASE SEE PREVIOUS PLANS AND ORIGINAL | | | PLANS INDICATED A 300A SERVICE. PLEASE | | | SEE SERVICE IS NOW BEING SHOWN AS | | | 400A'S. | | | | | | 3)NOTE: PLEASE SEE LOAD CALCULATIONS, | | | PLEASE SEE 4-A/C SYSTEMS SHOWN IN LOAD | | | CALCULATIONS, HOWEVER THIS DOES NOT | | | CORRELATE WITH PLANS.. | | | 215.5, 220 | | | | | | 4)NOTE: PLEASE SEE LOADS FOR EACH PANEL | | | IS SHOWN AS BLANK, | | | PLEASE SEE LOADS ARE SHOWN AS THE SAME | | | ON EACH PANEL SCHEDULE AND LOAD | | | CALCULATIONS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | |
|