Plan Review Notes
Plan Review Notes For Permit 04080905
Permit Number 04080905
Review Stop E
Sequence Number 3
Notes
Date Text
2005-08-17 00:00:00******** UNSAT *******
  
 1)NOTE: PLEASE SEE 310.15B6 FOR MIN
 CONDUCTORS FOR 200A PANELS.
  
 2)NOTE: PLEASE SEE 250.66,310.15B6, THE
 MIN GROUNDING ELECTRODE CONDUCTOR SIZE
 IS 1/0, PLEASE SEE #2 SHOWN NEEDS TO BE
 CORRECTED.
 PLEASE SEE PREVIOUS PLANS AND ORIGINAL
 PLANS INDICATED A 300A SERVICE. PLEASE
 SEE SERVICE IS NOW BEING SHOWN AS
 400A'S.
  
 3)NOTE: PLEASE SEE LOAD CALCULATIONS,
 PLEASE SEE 4-A/C SYSTEMS SHOWN IN LOAD
 CALCULATIONS, HOWEVER THIS DOES NOT
 CORRELATE WITH PLANS..
 215.5, 220
  
 4)NOTE: PLEASE SEE LOADS FOR EACH PANEL
 IS SHOWN AS BLANK,
 PLEASE SEE LOADS ARE SHOWN AS THE SAME
 ON EACH PANEL SCHEDULE AND LOAD
 CALCULATIONS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717