2004-08-24 00:00:00************ UNSAT ************
  
 1)NOTE: PLEASE CORRELATEPANELS/MCB
 FROM RISER AND PANELS .
 RISER SHOWS PANELS AS 150A'S AND PANELS
 INDICATE 200A?
 PLEASE ALSO SEE LOAD ON PANEL "A" IS
 ALREADY SHOWN AT 149.16A'S WITH ALL
 DERATING TAKEN.
  
 2)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING FROM MAINS TO PANELS.
 250.24,250.110,250.122
  
 3)NOTE: PLEASE SEE POOL PANEL IS SHOWN
 AS HAVING 10KW LOAD ON PANEL "A" YET
 POOL PANEL LOAD DOES NOT SHOW THIS?
  
 4 )NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 2002 NEC 210.12
 RECEPTS ARE THE AFCI PROTECTED ITEMS
 SHOWN ON PANELS AT THIS TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  