| Plan Review Notes For Permit 04080905 |
| Permit Number |
04080905 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-08-24 00:00:00 | ************ UNSAT ************ | | | | | | 1)NOTE: PLEASE CORRELATEPANELS/MCB | | | FROM RISER AND PANELS . | | | RISER SHOWS PANELS AS 150A'S AND PANELS | | | INDICATE 200A? | | | PLEASE ALSO SEE LOAD ON PANEL "A" IS | | | ALREADY SHOWN AT 149.16A'S WITH ALL | | | DERATING TAKEN. | | | | | | 2)NOTE: PLEASE SEE MISSING EQUIPMENT | | | GROUNDING FROM MAINS TO PANELS. | | | 250.24,250.110,250.122 | | | | | | 3)NOTE: PLEASE SEE POOL PANEL IS SHOWN | | | AS HAVING 10KW LOAD ON PANEL "A" YET | | | POOL PANEL LOAD DOES NOT SHOW THIS? | | | | | | 4 )NOTE: PLEASE LIST THE REQ'D ARC | | | FAULT PROTECTED CURCUIT(S) ON PANEL | | | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" | | | IN BEDROOMS ARE TO BE PROTECTED , | | | INCLUDING, LTS, RECEPTS, SD'S ETC. | | | 2002 NEC 210.12 | | | RECEPTS ARE THE AFCI PROTECTED ITEMS | | | SHOWN ON PANELS AT THIS TIME. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|