| Date |
Text |
| 2006-09-20 00:00:00 | *** UNSAT *** |
| | |
| | 1) NOTE: PLEASE SEE PLANS STILL SHOW AN |
| | INDIVIDUA METER ALONG WITH TWO MAINS |
| | WHICH IS HOW THE ORIGINAL RISER WAS |
| | SHOWN. IF THIS EQUIPMENT IS A METER/MAIN |
| | COMBO PANEL, THEN PLANS SHOW THIS ON |
| | PLANS ON THE SIDE OF THE DWELLING. |
| | 106.1.2 FBC. |
| | |
| | 2) NOTE: PLEASE SEE LOAD CALCULATIONS |
| | AND PLEASE SEE NEC 220.31. |
| | PLEASE SEE A/C LOADS MAY NOT BE DE-RATED |
| | IN WITH GEN LTS AND RECEPTS. A/C LOAD IS |
| | CURRENLTY BEING DE-RATED AT 65% AND THEN |
| | AGAIN AT 40%. |
| | PLEASE KNOW, BASED ON THE LOADS ON |
| | PANELS, THE LOAD FOR THE SERVICE IS |
| | SUBSTANTIALLY HIGHER THAN THE LOAD |
| | SHOWN. |
| | |
| | 3) NOTE: PLEASE SEE MISSIGN RECEPT IN |
| | BEDRM #4. |
| | MORE THAN 2' OF WALL REQUIRES A RECEPT. |
| | 210.52 |
| | |
| | 4) NOTE: PLEASE SEE 210.8A7, PLEASE SEE |
| | ANY RECEPT WITHIN 6FT OF THE SINK'S EDGE |
| | IN THE LAUNDRY RM IS REQUIRED TO BE GFI |
| | / GFI PROTECTED. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |