| 2006-08-11 00:00:00 | ********* UNSAT ********* |
| | |
| | ** PLEASE SEE SOME ITEMS ARE THE SAME AS |
| | COMMENTS WHICH WERE REDLINED ON PLANS IN |
| | "NOV 04". |
| | PLEASE ALSO SEE NEW COMMENTS AS PLANS |
| | HAVE BEEN REVISED. |
| | |
| | 1) NOTE: PLEASE SEE MIN GEC PER 250.66/ |
| | 310.15B6AS 1/0. THIS SIZE WAS REDLINED |
| | ON ORIGINAL PLANS. |
| | |
| | 2) NOTE: PLEASE SEE MISSING EQUIPMENT |
| | GROUNDING CONDUCTORS FROM THE MAINS TO |
| | THE SUBPANELS. |
| | 250.110.,250.24B,250.122 ETC. |
| | |
| | 3) NOTE: PLEASE CORRELATE PLANS WITH |
| | RISER. PLEASE SEE RISER NOW SHOWS WHAT |
| | APPEARS TO BE A METER/MAIN COMBO, YET |
| | NOT CLEAR AS NO MAIN IS SHOWN?? |
| | PLEASE SEE 230.70, PLEASE SEE PLANS |
| | STILL SHOWS TWO MAIN DISCONNECTS AS ON |
| | ORIG RISER. PLEASE SEE PLANS ARE NOT |
| | CLEAR FOR THE SCENARIO . WHERE IS THE |
| | OCP FOR PANEL "B", IS THERE FEED-THRU |
| | LUGS? ETC ETC. |
| | |
| | 4) NOTE: PLEASE SEE LOAD CALCULATIONS |
| | ARE NOT COMPLETE FOR ALL EQUIPMENT AND |
| | FOR SERVICE. PLEASE SEE NEC 220.31 ETC |
| | AS LOADS ARE NOT COMPLETED, A/C LOADS |
| | ARE NOT SHOWN IN CALCS WHICH MAY NOT BE |
| | DERATED WITH THE GEN LT/RECEPTS. |
| | PLEASE SEE LOADS FOR PANEL "B" ARE NOT |
| | SHOWN IN WITH THE OTHER. ETC. |
| | 408.4,310.16,240.4 230.70. |
| | |
| | 5) NOTE: PLEASE SEE MISSING REDLINED |
| | RECEPTS ON PLANS PER 210.52 |
| | |
| | 6) NOTE: PLEASE SEE MISSING POOL PANEL |
| | ON PLANS WHICH IS SHOWN ON RISER. |
| | FBC 106.1.2 ADMIN SECT. |
| | |
| | 7) NOTE: PLEASE SEE DISCONNECT |
| | CLEARENCES PER 110.26 FOR ALL |
| | DISCONNECTS. PLEASE SEE A/C EQUIPMENT |
| | SIDE OF HOUSE. |
| | |
| | 8) NOTE: PLEASE SEE PLANS NOW INCLUDE |
| | ALL NEW LV SKR WIRINGAND SPKRS WHICH |
| | WERE NOT ON ORIGINAL PLANS OR PERMIT. |
| | PLEASE SUBMIT THIE UNDER A SEPARATE |
| | PERMIT APPLICATION, PLANS AND FEES FOR |
| | COMPLETE SCOPE OF WORK. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |