| Date |
Text |
| 2004-08-25 00:00:00 | ************* UNSAT ***************** |
| | |
| | 1)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | * PLEASE EITHER ADD A SD IN WHAT APPEARS |
| | TO BE MASTER BEDRM OR MOVE ONE SHOWN |
| | IN HALLWAY INTO MASTER SLEEPING AREA. |
| | *PLEASE SEE MISSING SD ON FIRST FLR |
| | LEADING TO FLR ABOVE. |
| | |
| | 2)NOTE: PLEASE PROVIDE ROOM DESIGNATION |
| | ON ELECTRICAL PLANS. |
| | |
| | 3)NOTE: PLEASE SEE 210.52D FOR MISSING |
| | GFI ON FIRST FLR BATH. |
| | |
| | 4)NOTE: PLEASE SEE 210.52C3 FOR KITCHEN |
| | PENINSULAR. A RECEPT IS SHOWN BUT W/ |
| | OVERHANG OF KITCHEN COUNTERTOP THIS |
| | MAY NOT BE ABLE TO SERVE COUNTERSPACE. |
| | PLEASE ALSO SEE WALL SPACE AT SAME |
| | LOCATION PER 210.52 |
| | |
| | 5)NOTE: PLEASE SEE 210.52 FOR A FEW |
| | RECEPTS MISSING. 2' OF WALL SPACE ETC. |
| | |
| | 6) NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210.8A-6 |
| | **ISLAND** |
| | |
| | 7 )NOTE: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | 210.12B 2002 NEC.PLEASE SEE CIRCUITING |
| | |
| | 8)NOTE: PLEASE SEE RISER SHOWS AN |
| | EQUIPMENT FROM GUTTER TO MAINS/FIRST |
| | MEANS OF DISC. PLEASE SEE 250.24,250.6 |
| | AN EG IS NOT INSTALLED UNITL AFTER THE |
| | FIRST MEANS OF DISC. |
| | |
| | 9)NOTE: PLEASE SEE LOCATION OF SERVICE |
| | SHOWN ON PLANS. RISER SHOWS METER/GUTTER |
| | AND TWO MAIN DISC'S WHICH DO NOT APPEAR |
| | TO BE ABLE TO FIT IN LOCATION SHOWN. |
| | PLEASE SEE 110.26 |
| | |
| | 10)NOTE: PLEASE CLARIFY LOCATION ON |
| | SECOND FLR WHICH APPEARS TO HAVE BATH |
| | RM SHOWN WITH NO ELECTRICAL? ARE THESE |
| | RMS BEING BUILT AT THIS TIME? |
| | LTS ETC. 210.582,210.70 |
| | |
| | 11)NOTE: PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| | BE FIGURED IN W/ 3W/PER SQ FT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND. |
| | PLEASE SEE LOAD CALCULATIONS ARE NOT |
| | SHOWN PER 220.31 . IT HAS BEEN NOTED |
| | THAT LIGNING IS BEING SHOWN AS A CONNECT |
| | -ED LOAD. PLEASE VERIFY WATTAGE OF |
| | FIXTURES AND PLEASE SEE FBC FOR REQUIRED |
| | "AIR-LOCK" TYPE FIXTURES. NOTE: MOST |
| | OF THESE TYPE OF FIXTURES ARE A MAX OF |
| | 75W. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |