| Plan Review Notes For Permit 04080838 |
| Permit Number |
04080838 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2005-03-31 00:00:00 | *** UNSAT 2ND REVIEW *** | | | | | | PLEASE SEE SOME ITEMS FROM PREVOUS | | | REVIEW STILL NEED CORRECTING. | | | | | | 1)NOTE: PLEASE SEE BATH CIRCUIT IS STILL | | | SHOWN AS 20A (REQ'D) ON #14 AWG WHICH IS | | | ONLY RATED FOR 15A'S. | | | 210.52D,210.11C3 | | | | | | | | | 2)NOTE: PLEASE SEE ONLY 1-#12 CONDUCTOR | | | IS SHOWN FEEDING SPRINKLER TIME CLOCK. | | | PLEASE VERIFY THIS? (MISPRINT). | | | THERE SOULD BE MORE THAN ONE CONDUCTOR | | | FEEDING TIME CLOCK. | | | | | | 3)NOTE: PLEASE SEE FOUNDATION STEEL HAS | | | NOW BEEN REMOVED FROM RISER DIAGRAM FOR | | | REQUIRED FOOTER STEEL CONNECTION. | | | PLEASE SEE UNDER 250.50 FOR NEW | | | CONSTRUCTION FOOTER/FOUNDATION STEEL IS | | | REQUIRED. | | | THIS IS THE RESONSIBLITY OF THE | | | ELECTRICAL CONTRACTOR TO INSTALL AS IT | | | WAS DETAILED ON THE ORIGINAL PLANS AS | | | SET-FORTH BY THE ENGINEER OF RECORD AND | | | IS REQUIRED UNDER NEC. | | | THIS SHALL BE SHOWN ON PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 |
|