Plan Review Notes
Plan Review Notes For Permit 04080838
Permit Number 04080838
Review Stop E
Sequence Number 4
Notes
Date Text
2005-03-31 00:00:00*** UNSAT 2ND REVIEW ***
  
 PLEASE SEE SOME ITEMS FROM PREVOUS
 REVIEW STILL NEED CORRECTING.
  
 1)NOTE: PLEASE SEE BATH CIRCUIT IS STILL
 SHOWN AS 20A (REQ'D) ON #14 AWG WHICH IS
 ONLY RATED FOR 15A'S.
 210.52D,210.11C3
  
  
 2)NOTE: PLEASE SEE ONLY 1-#12 CONDUCTOR
 IS SHOWN FEEDING SPRINKLER TIME CLOCK.
 PLEASE VERIFY THIS? (MISPRINT).
 THERE SOULD BE MORE THAN ONE CONDUCTOR
 FEEDING TIME CLOCK.
  
 3)NOTE: PLEASE SEE FOUNDATION STEEL HAS
 NOW BEEN REMOVED FROM RISER DIAGRAM FOR
 REQUIRED FOOTER STEEL CONNECTION.
 PLEASE SEE UNDER 250.50 FOR NEW
 CONSTRUCTION FOOTER/FOUNDATION STEEL IS
 REQUIRED.
 THIS IS THE RESONSIBLITY OF THE
 ELECTRICAL CONTRACTOR TO INSTALL AS IT
 WAS DETAILED ON THE ORIGINAL PLANS AS
 SET-FORTH BY THE ENGINEER OF RECORD AND
 IS REQUIRED UNDER NEC.
 THIS SHALL BE SHOWN ON PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717