| 2005-03-14 00:00:00 | *** UNSAT *** |
| | |
| | **PLEASE SEE THERE HAVE BEEN NUMEROUS |
| | CHANGES TO ORIGINAL ELECTRICAL PLANS |
| | WHICH HAVE NOW GENERATED NEW COMMENTS.** |
| | |
| | 1)NOTE: PLEASE SEE BATH CIRCUIT IS NOW |
| | SHOWN AS 20A (REQ'D) ON #14 AWG WHICH IS |
| | ONLY RATED FOR 15A'S. |
| | 210.52D,210.11C3 |
| | |
| | 2)NOTE: PLEASE SEE DINING RM RECEPTS ARE |
| | NOW SHOWN ON A 15A #14 AWG CIRCUIT. |
| | PLEASE SEE 210.52B1. DINING RM ETC REQ'D |
| | TO BE 20, #12. |
| | IN THE KITCHEN, PANTRY, BREAKFAST ROOM, |
| | DINING ROOM, OR SIMILAR AREA OF A |
| | DWELLING UNIT, THE TWO OR MORE 20-AMPERE |
| | SMALL-APPLIANCE BRANCH CIRCUITS REQUIRED |
| | BY 210.11(C)(1) SHALL SERVE ALL |
| | RECEPTACLE OUTLETS COVERED BY 210.52(A) |
| | AND (C) AND RECEPTACLE OUTLETS FOR |
| | REFRIGERATION EQUIPMENT. |
| | |
| | 3)NOTE: PLEASE SEE DISCONNETCS FOR A/C |
| | COND UNITS ARE NOW SHOWN DIRECTLY BEHIND |
| | CU'S. |
| | ORIG PLAN, DISC'S SHOWN TO MEET 110.26. |
| | |
| | 4)NOTE: PLEASE SEE MISSING EQUIPMENT |
| | GROUNDING CONDUCTOR TO POOL SUB PANEL |
| | FROM METER/MAIN COMBO. |
| | 250.110,250.122 ETC. |
| | |
| | 5)NOTE: PLEASE SEE ONLY 1-#12 CONDUCTOR |
| | IS SHOWN FEEDING SPRINKLER TIME CLOCK. |
| | PLEASE VERIFY THIS? (MISPRINT). |
| | |
| | 6)NOTE: PLEASE SEE ORIGINAL PLANS |
| | INDICATED 17-RECESSED LTS ON PANEL |
| | SCHEDULE AND 17-RECESSED FIXTURES WERE |
| | SHOWN ON PLANS. PLEASE SEE PANEL |
| | SCHEDULE NOW INDCIATES 28-RECESSED |
| | FIXTURES, HOWEVER PLANS STILL ONLY |
| | INDICATE 17-FIXTURES?? |
| | PLEASE CORRELATE # OF FIX'S ON PANEL |
| | SCHEDULE WITH PLANS. |
| | 215.5 |
| | |
| | ** NOTE** |
| | PLEASE SEE PLANS INDICATE WASHER AND |
| | DRYER AS "OPTIONAL". PLEASE SEE PLANS |
| | ARE REQUIRED TO HAVE ALL REVISIONS AND |
| | OPTIONS SUBMITTED FOR REVIEW BEFORE |
| | ROUGH ELECTRICAL INSPECTION. |
| | PLEASE ALSO NEC REQUIRES A MIN LAUNDRY |
| | CIRCUIT.1.5VA |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |