| Plan Review Notes For Permit 04080816 |
| Permit Number |
04080816 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-09-21 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2.)THE CA NUMBER FOR MORRISON | | | HERSCHFELD IS REQUIRED ON THE CALCS | | | FAC61G15-23.002. | | | | | | 3.)THE CALCS REFER TO THE IBC AS THE | | | BUILDING CODE. | | | | | | 4.)PROVIDE DESIGN PRESSURE REQUIREMENT | | | FOR THE ROOF.SUBMIT PRODUCT APPROVAL | | | FOR THE MEMBRANE (TEST REPORT AND | | | FLORIDA STATE OR LOCAL PRODUCT APPROVAL | | | FAC9B72, WWW.FLORIDABUILDING.ORG). | | | | | | 5.)PENETRATIONS THROUGH THE STAIR | | | ENCLOSURE ARE PROHIBITED BY FBC1006.1.3. | | | 1. | | | | | | 6.)RAILING TO COMPLY WITH FBC1608.1.2. | | | 1.SPECIFY; DO NOT QUOTE CODE REFERENCE | | | NUMBER ONLY. |
|