Plan Review Notes
Plan Review Notes For Permit 04080784
Permit Number 04080784
Review Stop E
Sequence Number 1
Notes
Date Text
2004-08-30 00:00:00************ UNSAT ***************
  
 1)NOTE: PLEASE PROVIDE ALL LICENSE
 INFORMATION ON TITLE BLOCK PER 61G1-16.-
 -.004 AS REQUIRED UNDER FS 481.219
 THIS IS REQUIRED ON ALL SHEETS WHEATHER
 OR NOT COMMENT IS MADE BY OTHER REVIEW-
 -ERS.
  
 2)NOTE: PLEASE SEE ALL RECEPTS W/ THE
 EXCEPTION OF ONE ARE ALL SHOWN ON THE
 SAME CIRCUIT?
 PLEASE CLARIFY
 PLEASE ALSO SEE NEC 220.13 FOR 180 VA
 PER RECEPT AND SEE MAX LOADING OF A
 15A OR 20A CIRCUIT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]