| Plan Review Notes For Permit 04080780 |
| Permit Number |
04080780 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-01-05 00:00:00 | BUILDINIG PLAN REVIEW: FAILED | | | | | | 1. THE OWNER/AGENT STILL HAS NOT SIGNED | | | THE ENERGY FORM. | | | | | | 2.THE DADE COUNTY PRODUCT APPROVAL FOR | | | THE ARCH WINDOWS FOR THE BUTT GLASS | | | ASSEMBLY NEEDS TO BE SUBMITTED. THE | | | GLASS IS NOT IMPACT AND WILL REQUIRE | | | STORM PANEL PROTECTION. ACCORDING TO | | | THE | | | ENGINEER THE ARCH 4500 SERIES WINDOWS | | | ARE TO BE USED IN THIS ASSEMBLY. | | | | | | 3. THE APPLICATION FOR THE SITE | | | SPECIFIC | | | PRODUCT APPROVAL IS INCOMPLETE FOR THE | | | BUTT GLASS WINDOWS.THE ENGINEER CANNOT | | | BE THE TECHNICAL REPRESENTATIVE (6) AND | | | (7) APPROVED THIRD PARTY QUALITY | | | ASSURANCE ENTITY LISTED WITH THE STATE. | | | THIS IS A CONFLICT OF INTEREST. THE | | | DADE | | | COUNTY PRODUCT APPROVAL FOR THE ARCH | | | 4500 SERIES SHOULD BE SUBMITTED WITH | | | THE | | | SITE SPECIFIC APPLICATION. | | | | | | 4. THERE IS STILL A BALANCE OF $753.65 | | | IN PERMIT FEES DUE. | | | | | | ANY QUESTIONS PLEASE CALL: | | | LEA SMITH, BUILDING PLANS EXAMINER | | | 805-6713 |
|