| Plan Review Notes For Permit 04080749 |
| Permit Number |
04080749 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-12-21 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE PERSON RESONSIBLE FOR THE PLANS | | | MUST PRINT AND SIGN THEIR NAME TO SAME | | | PER 104.2.1 FBC. | | | | | | 2} THE INFORMATION ON THE PANELBOARD HAS | | | BEEN REMOVED, PLEASE REPLACE. | | | | | | 3} THE ELECTRICAL RISER GROUNDING | | | ELECTRODE CONDUCTOR SYSTEM MUST COMPLY | | | WITH 250.50 FOR THE RELOCATED METER. | | | | | | 4} THERE ARE SEVERAL APPLIANCES ON THE | | | PANEL SCHEDULE NOT LISTED IN THE | | | CALCULATIONS. SEE 330.31. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|