| Plan Review Notes For Permit 04080749 |
| Permit Number |
04080749 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-09-01 00:00:00 | PROVISO: | | | 1.PER 2001 FBC(M) 307.2.3, AUXILIARY | | | DRAIN PAN WITH OVERFLOW PROTECTION | | | REQUIRED. | | | | | | 2.A MINIMUM OF 4" CLEARANCE AROUND THE | | | AHU IS REQUIRED PER 2001 FBC(M) 603.1.3. | | | | | | 3.RETURN AIR REQUIRED FROM BEDROOM | | | AREAS PER 2001 FBC(M) 601.4.SEE THE | | | ATTACHED SCHEDULE FOR PROPER SIZING. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|