Plan Review Notes
Plan Review Notes For Permit 04080749
Permit Number 04080749
Review Stop M
Sequence Number 1
Notes
Date Text
2004-09-01 00:00:00PROVISO:
 1.PER 2001 FBC(M) 307.2.3, AUXILIARY
 DRAIN PAN WITH OVERFLOW PROTECTION
 REQUIRED.
  
 2.A MINIMUM OF 4" CLEARANCE AROUND THE
 AHU IS REQUIRED PER 2001 FBC(M) 603.1.3.
  
 3.RETURN AIR REQUIRED FROM BEDROOM
 AREAS PER 2001 FBC(M) 601.4.SEE THE
 ATTACHED SCHEDULE FOR PROPER SIZING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.