2005-03-23 00:00:00PLAN DENIED
 1) SEER ON ENERGY CALCULATIONS DO NOT
 MATCH PLAN.
 2)MECHANICAL PLANS NEED ENGINEER SEAL IF
 THE PLAN IS ON ENGINEER PAPER.
 3) MEED DUCT SIZE ON TRUNK LINE OVER
 MASTER BED ROOM OR SIZE OF RETURN AIR IN
 MASTER.
 4) NEED CFM AT ALL SUPPLY GRILS.