| Plan Review Notes For Permit 04080743 |
| Permit Number |
04080743 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-08-25 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) SANITARY RISER DIAGRAM DOES NOT RE- | | | FLECT THE FLOOR PLAN, NOR DOES IT MEET | | | CODE REQUIREMENTS. | | | A) MISSING FIXTURES 104.2.1 | | | B) MISSING PIPE SIZES 104.2.1 | | | C) SINK DRAINING THROUGH WET VENT 909.1 | | | | | | 2) SUGGEST THE PLUMBING CONTRACTOR LAY- | | | OUT RISER DIAGRAM AND ENGINEER REDRAW | | | AND INCORPORATE ON TO PLANS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|