2004-08-25 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SANITARY RISER DIAGRAM DOES NOT RE-
 FLECT THE FLOOR PLAN, NOR DOES IT MEET
 CODE REQUIREMENTS.
 A) MISSING FIXTURES 104.2.1
 B) MISSING PIPE SIZES 104.2.1
 C) SINK DRAINING THROUGH WET VENT 909.1
  
 2) SUGGEST THE PLUMBING CONTRACTOR LAY-
 OUT RISER DIAGRAM AND ENGINEER REDRAW
 AND INCORPORATE ON TO PLANS.
  