Plan Review Notes
Plan Review Notes For Permit 04080743
Permit Number 04080743
Review Stop E
Sequence Number 1
Notes
Date Text
2004-08-24 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SHOW THE LOCATION OF"EXISTING
 MAIN 200 AMPS" ON THE PLAN. SHOWS ON
 RISER ONLY.
  
 2} THE ELECTRIC PANEL IN THE BATHROOM
 ISIN VIOLATION OF 240.24(E) AND MUST BE
 RELOCATED OR ENCLOSED.
  
 3} THE NEW PANEL LOCATION IN THE LAUNDRY
 ROOM DOES NOT COMPLY WITH 110.26
 CLEARANCE REQUIREMENTS.
  
 4} THE RECEPTACLES IN THE MASTER BATH
 MUST SHOW COMPLIANCE WITH 210.52(D)
 LOCATION, 210.8(A)(1) GFI.
  
 5} PLEASE LIST ALL THE REQUIRED
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.11(C)(3).
  
 6} PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CIRCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 7} PLEASE SEE REVIWED PLANS FOR
 RECEPTACLES MISSING IN LIVING ROOM,
 DINING ROOM (210.52(B)(1)), DEN AND
 ADDITION PER 210.52(A)(1) & (2).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026