| Plan Review Notes For Permit 04080743 |
| Permit Number |
04080743 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-08-24 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE SHOW THE LOCATION OF"EXISTING | | | MAIN 200 AMPS" ON THE PLAN. SHOWS ON | | | RISER ONLY. | | | | | | 2} THE ELECTRIC PANEL IN THE BATHROOM | | | ISIN VIOLATION OF 240.24(E) AND MUST BE | | | RELOCATED OR ENCLOSED. | | | | | | 3} THE NEW PANEL LOCATION IN THE LAUNDRY | | | ROOM DOES NOT COMPLY WITH 110.26 | | | CLEARANCE REQUIREMENTS. | | | | | | 4} THE RECEPTACLES IN THE MASTER BATH | | | MUST SHOW COMPLIANCE WITH 210.52(D) | | | LOCATION, 210.8(A)(1) GFI. | | | | | | 5} PLEASE LIST ALL THE REQUIRED | | | DEDICATED BATH(S) CIRCUIT(S) ON PANEL | | | SCHEDULE. PER 210.11(C)(3). | | | | | | 6} PLEASE LIST THE REQUIRED ARC | | | FAULT PROTECTED CIRCUIT(S) ON PANEL | | | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" | | | IN BEDROOMS ARE TO BE PROTECTED , | | | INCLUDING, LTS, RECEPTS, SD'S ETC. | | | | | | 7} PLEASE SEE REVIWED PLANS FOR | | | RECEPTACLES MISSING IN LIVING ROOM, | | | DINING ROOM (210.52(B)(1)), DEN AND | | | ADDITION PER 210.52(A)(1) & (2). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|