| Date |
Text |
| 2004-10-21 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | |
| | COMMENTS FROM THE PREVIOUS REVIEW HAVE |
| | NOT BEEN ADDRESSED, OR HAVE NOT BEEN |
| | ADDRESSED PROPERLY. NUMBER OF PREVIOUS |
| | REVIEW COMMENTS WILL REMAIN THE SAME TO |
| | AVOID CONFUSION. |
| | 1) THERE IS MORE WORK SHOWN ON THE PLAN |
| | THAN IS SHOWN ON THE APPLICATION. PLEASE |
| | CALRIFY. SECTION 104.2.1 |
| | 4) SHOW THE FOLLOWING INFORMATION ON THE |
| | ACCESSIBLE TOILET DETAIL. 11-4.16.3 |
| | CLEAR FLOOR SPACE, 11-4.19.3 CLEAR FLOOR |
| | SPACE. |
| | 5) A WATER RISER DIAGRAM IS REQUIRED PER |
| | SECTION 104.3.1.1. - THE SANITARY RISER |
| | DIAGRAM SUBMITTED DOES NOT REFLECT THE |
| | FLOOR PLAN. RISER SHOWS TWO W/C'S AND |
| | TWO LAV'S, BUT FLOOR PLAN SHOWS ONE W/C |
| | AND ONE LAV. PLEASE SHOW SECOND TOILET |
| | ROOM CAPPED OFF. SECTION 104.2.1 |
| | |
| | *********WHEN RESUBMITTING PLANS******** |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |