| Notes |
| Date |
Text |
| 2004-11-05 00:00:00 | THE COMMENTS FROM THE LAST REVIEW WHERE | | | NOT ANSWERED.PLEASE PROVIDE THE | | | FOLLOWING INFORMATION FOR REVIEW. | | | | | | 1} THE FEEDER AND OVERCURRENT PROTECTION | | | FOR THE "SUB-PANEL" NOW SHOWN AS BEING | | | FED WITH "3/0 OCP"? | | | | | | 2} PROVIDE A SCHEDULE FOR THE | | | "SUB-PANEL" AS REQUESTED IN THE FIRST | | | REVIEW. | | | | | | 3} THE MAIN SERVICE ON THE SCHEMATIC IS | | | SHOWN AS A 200 AMP, THE LOAD CALCULATION | | | SUPPLIED INDICATES A 250 AMP PANEL. | | | PLEASE CLARIFY. | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|