| Plan Review Notes For Permit 04080668 |
| Permit Number |
04080668 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-09-16 00:00:00 | 1) COULD NOT LOCATE ANY EMERGENCY | | | LIGHT FIXTURES WITHIN THE SPACE. | | | | | | 2) SEPARATE PLANS AND PERMIT REQUIRED | | | FOR FIRE ALARM SYSTEM REMODEL. | | | | | | 3) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR FIRE SPRINKLER SYSTEM REMODEL. | | | | | | 4) DETERMINE IF AN EXISTING FIRE | | | SPRINKLER HEAD IS PRESENT IMMEDIATELY | | | OUTSIDE OF ENTRY DOORS. | | | | | | 5) PLEASE INDICATE LOCATIONS OF EXISTING | | | OR NEW FIRE RATED DEMISING WALLS. | | | PLEASE PROVIDE UL NUMBERS. | | | | | | 6) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILINGS. | | | ALSO PROVIDE FLAMESPREAD DETAILS ON | | | STRETCHED WHITE FABRIC MATERIAL. | | | | | | 7) PLEASE INDICATE FIRE EXTINGUISHER | | | LOCATIONS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|