2004-08-20 00:00:00BUILDING PLAN REVIEW
 PERMIT:04080636
 ADD: 622 N. FLAGLER DR.
 CONT:THE PLACE FOR TILE, INC.
 TEL: (305)528-7275
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 2ND REVIEW
 ACTION: DENIED
  
 1) IF FLOORING TILE OR MARBLE IS 3/8"
 THICK AND INSTALL WITH THINSET THAT"S
 FINE, BUT IF THE TILE OR MARBLE IS
 MORE THAN 3/8" AND DYRPACK IS USED, A
 CERTIFIED ENGINEER HAS TO APPROVE THE
 FLOORING DESIGN DUE TO THE LOAD
 BEARING ISSUE. SEE FBC.1603.1 ALSO SEE
 FAC.SEC 61G15-23.002.
 THE ENGINEER HAS TO SIGNED AND SEAL THE
 LETTER.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  