Plan Review Notes For Permit 04080627
Permit Number 04080627
Review Stop E
Sequence Number 2
Notes
Date Text
2005-02-24 00:00:00********** UNSAT ************
  
 1)NOTE: PLEASE INCLUDE FOOTER STEEL AND
 COLD WATER FOR GROUNDING ELECTRODE AT
 DETACHED BLDG.250.32,250.50
 PLEASE SEE MISSING #8 EQUIPMENT GRND
 FROM EXISTING MAIN PANEL TO
 J-BOX.250.122
  
 2)NOTE: PLEASE SEE NEW PANEL SCHEDULE
 SUBMITTED, SHOULD INCLUDE AWG FOR BRANCH
 CIRCUITS ALONG WITH OCP.
  
 3)NOTE: PLEASE SEE ARC FAULT PROTECTION
 WILL BE REQUIRED FOR LIV RM/ ADAPTABLE
 SLEEPING RM.
 210.12
  
 4)NOTE: PLEASE VERIFY IF NEW WASHER AND
 DRYER IS REPLACING EXSITNG? PLEASE SEE
 LOAD CALCS INCLUDE ONE ONLY?
  
 5)NOTE: PLEASE SEE 220.31B FOR LOAD
 CALCS.
  
 6)NOTE: PLEASE SEE CONDUIT FILL FOR 1"
 SCHEDULE 80, 3#4'S AND 1#8. PLEAS
 INCREASE TO 1 1/4".
  
  
 PLEASE SEE BLDG COMMENTS FOR NOC EXPIRED
 PER FS 713
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  