| Plan Review Notes For Permit 04080627 |
| Permit Number |
04080627 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-02-24 00:00:00 | ********** UNSAT ************ | | | | | | 1)NOTE: PLEASE INCLUDE FOOTER STEEL AND | | | COLD WATER FOR GROUNDING ELECTRODE AT | | | DETACHED BLDG.250.32,250.50 | | | PLEASE SEE MISSING #8 EQUIPMENT GRND | | | FROM EXISTING MAIN PANEL TO | | | J-BOX.250.122 | | | | | | 2)NOTE: PLEASE SEE NEW PANEL SCHEDULE | | | SUBMITTED, SHOULD INCLUDE AWG FOR BRANCH | | | CIRCUITS ALONG WITH OCP. | | | | | | 3)NOTE: PLEASE SEE ARC FAULT PROTECTION | | | WILL BE REQUIRED FOR LIV RM/ ADAPTABLE | | | SLEEPING RM. | | | 210.12 | | | | | | 4)NOTE: PLEASE VERIFY IF NEW WASHER AND | | | DRYER IS REPLACING EXSITNG? PLEASE SEE | | | LOAD CALCS INCLUDE ONE ONLY? | | | | | | 5)NOTE: PLEASE SEE 220.31B FOR LOAD | | | CALCS. | | | | | | 6)NOTE: PLEASE SEE CONDUIT FILL FOR 1" | | | SCHEDULE 80, 3#4'S AND 1#8. PLEAS | | | INCREASE TO 1 1/4". | | | | | | | | | PLEASE SEE BLDG COMMENTS FOR NOC EXPIRED | | | PER FS 713 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | |
|