| 2004-08-23 00:00:00 | | | | PROVISO | | | ~~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | THE INTENT OF THIS PROVISO IS TO ALLOW | | | WORK TO BEGIN WHILE DETERMINATION OF | | | DEVICE LOCATION IS MADE PER ACTUAL | | | FIELD CONDITIONS. THE PLANS SUBMITTED | | | NEED TO HAVE ADDITIONAL INFORMATION. | | | PROVIDE A REVISED SET OF PLANS WITH THE | | | FOLLOWING PRIOR TO CALLING A ROUGH | | | INSPECTION. | | | | | | 1} INDICATE THE LOCATION OF ALL SERVICE | | | EQUIPMENT. | | | | | | 2} LABEL ALL ROOMS. INDICATE DOOR | | | LOCATIONS SO COMPLIANCE WITH 210.70 CAN | | | BE DETERMINED. ALSO SHOW LIGHT AND | | | SWITCHING DEVICE LOCATION. | | | | | | 3} INDICATE COMPLIANCE WITH 210.52(E) & | | | 210.63. | | | | | | 4} INCLUDE OCP AND CONDUCTOR SIZE ON THE | | | PANEL SCHEDULE. | | | | | | 5} INDICATE COMPLIANCE WITH 210.12 AND | | | 210.11(C)(3) ON THE PANEL SCHEDULE. | | | | | | THE DESIGNER OF RECORD RESPONSIBLE FOR | | | THE DRAWING SHALL PRINT AND SIGN NAME | | | ON SAME, FBC 104.2.1. | | | | | | ALLOW 2-3 DAYS AFTER SUBMITTING ABOVE | | | FOR REVIEW. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|