| Plan Review Notes For Permit 04080598 |
| Permit Number |
04080598 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-08-23 00:00:00 | ******** UNSAT *********** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110.9/215.5 | | | | | | 2)NOTE: PLEASE SEE MISSING EQUIPMENT | | | GRND FROM MAIN TO PANEL. 250.24,250.110, | | | 250.122. | | | | | | 3)NOTE: PLEASE SEE MISSING RECEPT FOR | | | 2' OF WALL. REDLINED ON ONE SET. | | | | | | 4)NOTE: PLEASE SEE 220.16 FOR MIN OF 1.5 | | | KW FOR LAUNDRY LOAD. SHOWN AS 1.2KW. | | | | | | 5 )NOTE: PLEASE LIST THE REQ'D ARC | | | FAULT PROTECTED CURCUIT(S) ON PANEL | | | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" | | | IN BEDROOMS ARE TO BE PROTECTED , | | | INCLUDING, LTS, RECEPTS, SD'S ETC. | | | NOTE MENTIONS RECEPTS ONLY. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|