| Plan Review Notes For Permit 04080588 |
| Permit Number |
04080588 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-10-14 00:00:00 | DENIED: | | | 1.PROVIDE REVISED OUTSIDE AIR | | | CALCULATIONS PER 2001 FBC(M) 403.3. | | | | | | 2.PROVIDE AIR BALANCE SCHEDULE IN | | | ACCORDANCE WITH 2001 FBC(M) 501.4. | | | | | | HOOD REVIEW: | | | PLEASE NOTE, PLANS SUBMITTED WITH THE | | | BUILDING APPLICATION.ADDITIONAL PERMIT | | | REQUIRED FOR THE HOOD.ADDITIONAL PLANS | | | AND PERMIT REQUIRED FOR THE FIRE | | | SUPPRESSION. | | | | | | 1.PLEASE INDICATE HOW COMPLIANCE WITH | | | 506.3.10, WILL BE MET.SHOW ACCESS TO | | | CLEANOUTS. | | | | | | 2.WELDS ARE TO BE INSPECTED PRIOR TO | | | COVERING. | | | | | | 3.A MINIMUM SLOPE OF 1/4" PER FT | | | REQUIRED FOR THE GREASE DUCT IN | | | ACCORDANCE WITH 2001 FBC(M) 506.3.9. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|