Plan Review Notes
Plan Review Notes For Permit 04080588
Permit Number 04080588
Review Stop P
Sequence Number 1
Notes
Date Text
2004-09-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) METRO DESIGN GROUP SHOWN ON TITLE
 BLOCK. SUBMIT A CERTIFICATE OF AUTHORI-
 ZATION AS REQUIRED BY FAC 61G15-23.002 &
 FS 471.025.
 2) DPBR STAMP IS REQUIRED ON BOTH SETS
 OF PLANS AND A COPY OF THE DBPR WORK
 SHEET REQUIRED ON EACH SET OF PLANS.
 SECTION 101.4.7
 3) SHTS A-3.2 & A-3.4 DISH WASHER SHALL
 DISCHARGE INTO THE SANITARY SYSTEM, NOT
 THE GREASE SYSTEM AS SHOWN. CITY UTILITY
 REQUIREMENT.
 4) SHT A-3.4 GREASE/SANITARY RISERS:
 SECTION 704.2 THE SIZE OF THE DRAINAGE
 PIPE SHALL NOT BE REDUCED IN THE DIRECT-
 ION OF THE FLOOR. MANY 3" FLOOR SINKS
 ARE DRAINING INTO 2" DRAIN LINES.
 5) SHT A-3.4 GREASE/SANITARY RISERS,
 SHOW ALL PIPE SIZES THROUGHOUT EACH SYS-
 TEM. SECTION 104.2.1
 6) SUBMIT MANUFACTURE SPECIFICATION FOR
 EACH WASTE PUMP. EACH PUMP SHALL BE VEN-
 TED TO ATMOSPHERE. - SECTION 916.5
 7) WASTE PUMPS SHALL HAVE A CHECK VALVE
 WITH A GATE VALVE ON THE DISCHARGE SIDE
 OF THE CHECK VALVE. SECTION 712.2
 8) SHT A-3.4 PLUMBING NOTES:
 #8 MINIMUM 1/4" FT. REQUIRED FOR 2-1/2"
 AND SMALLER PIPE. CORRECT NOTE. SECTION
 104.2.1 - TABLE 704.1
 #12 AIR CHAMBERS ARE NOT APPROVED. DE-
 LETE FROM REFERENCE. SECTION 604.9
 9) A WATER RISER DIAGRAM IS REQUIRED PER
 SECTION 104.3.1.1.
 10) INDICATE MINIMUM FIXTURES PER TABLE
 1003.1. ARE SEATS FIXED OR NOT FIXED?
 11) THE FOLLOWING INFORMATION IS REQUIR-
 ED FOR THE GAS PERMIT.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE. - SOME PIPE SIZES AND THE
 LENGTHS ARE NOT SHOWN.
 B. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3). - INDICATE
 THE DISTANCE FROM L/P TANK TO SECOND
 STAGE (2 PSI - .5 PSI) REGULATOR. - THE
 DISTANCE FROM THE SECOND STAGE REGULAT-
 ORS AND MOST REMOTE FIXTURE IS SHOWN AS
 APPROX. 100', BUT ADDS UP TO APPROX 148'
 PLEASE CLARIFY.
 C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 D. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 E. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 F. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 G) SUBMIT MANUF. SPECIFICATIONS FOR THE
 THE GAS REGULATORS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]