| Date |
Text |
| 2004-09-15 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 BUILDING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1) METRO DESIGN GROUP SHOWN ON TITLE |
| | BLOCK. SUBMIT A CERTIFICATE OF AUTHORI- |
| | ZATION AS REQUIRED BY FAC 61G15-23.002 & |
| | FS 471.025. |
| | 2) DPBR STAMP IS REQUIRED ON BOTH SETS |
| | OF PLANS AND A COPY OF THE DBPR WORK |
| | SHEET REQUIRED ON EACH SET OF PLANS. |
| | SECTION 101.4.7 |
| | 3) SHTS A-3.2 & A-3.4 DISH WASHER SHALL |
| | DISCHARGE INTO THE SANITARY SYSTEM, NOT |
| | THE GREASE SYSTEM AS SHOWN. CITY UTILITY |
| | REQUIREMENT. |
| | 4) SHT A-3.4 GREASE/SANITARY RISERS: |
| | SECTION 704.2 THE SIZE OF THE DRAINAGE |
| | PIPE SHALL NOT BE REDUCED IN THE DIRECT- |
| | ION OF THE FLOOR. MANY 3" FLOOR SINKS |
| | ARE DRAINING INTO 2" DRAIN LINES. |
| | 5) SHT A-3.4 GREASE/SANITARY RISERS, |
| | SHOW ALL PIPE SIZES THROUGHOUT EACH SYS- |
| | TEM. SECTION 104.2.1 |
| | 6) SUBMIT MANUFACTURE SPECIFICATION FOR |
| | EACH WASTE PUMP. EACH PUMP SHALL BE VEN- |
| | TED TO ATMOSPHERE. - SECTION 916.5 |
| | 7) WASTE PUMPS SHALL HAVE A CHECK VALVE |
| | WITH A GATE VALVE ON THE DISCHARGE SIDE |
| | OF THE CHECK VALVE. SECTION 712.2 |
| | 8) SHT A-3.4 PLUMBING NOTES: |
| | #8 MINIMUM 1/4" FT. REQUIRED FOR 2-1/2" |
| | AND SMALLER PIPE. CORRECT NOTE. SECTION |
| | 104.2.1 - TABLE 704.1 |
| | #12 AIR CHAMBERS ARE NOT APPROVED. DE- |
| | LETE FROM REFERENCE. SECTION 604.9 |
| | 9) A WATER RISER DIAGRAM IS REQUIRED PER |
| | SECTION 104.3.1.1. |
| | 10) INDICATE MINIMUM FIXTURES PER TABLE |
| | 1003.1. ARE SEATS FIXED OR NOT FIXED? |
| | 11) THE FOLLOWING INFORMATION IS REQUIR- |
| | ED FOR THE GAS PERMIT. |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. - SOME PIPE SIZES AND THE |
| | LENGTHS ARE NOT SHOWN. |
| | B. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). - INDICATE |
| | THE DISTANCE FROM L/P TANK TO SECOND |
| | STAGE (2 PSI - .5 PSI) REGULATOR. - THE |
| | DISTANCE FROM THE SECOND STAGE REGULAT- |
| | ORS AND MOST REMOTE FIXTURE IS SHOWN AS |
| | APPROX. 100', BUT ADDS UP TO APPROX 148' |
| | PLEASE CLARIFY. |
| | C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2 |
| | D. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | E. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND |
| | APPURTENANCES PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | F. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | G) SUBMIT MANUF. SPECIFICATIONS FOR THE |
| | THE GAS REGULATORS. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |