| 2004-08-27 00:00:00 | DENIED: |
| | HVAC REVIEW |
| | 1.SHEET A3.5 INDICATES A NOTE ON THE FAN |
| | COIL DETIAL "NOT APPROVED" PLEASE |
| | CLARIFY. |
| | |
| | 2.SHEET A3.5 FAN COIL EQUIPMENT SCHEDULE |
| | INDICATES NEW FAN COIL WITH DUCT SMOKE |
| | DETECTOR.PLEASE VERIFY EXISTING FAN |
| | COILS THAT HAVE THE CAPACITY TO EXCEED |
| | 2,000 CFM ARE EQUIPPED WITH DUCT SMOKE |
| | DETECTORS. |
| | |
| | HOOD REVIEW: |
| | PLEASE NOTE ADDITIONAL PERMITS REQUIRED |
| | FOR HOOD, FIRE SUPPRESSION AND WALK-IN |
| | COOLERS.THE FOLLOWING COMMENTS ARE |
| | FOR THE PLANS SUBMITTED FOR THE HOOD AND |
| | GREASE DUCT. |
| | |
| | 1.PLAN SHEET A3.5 HIBACHI TABLE |
| | EXHAUST.DETAIL INDICATES GREASE DUCT |
| | SHARING THE SAME SHAFT.PER 2001 FBC(M) |
| | 506.3.12 & 2001 NFPA 96 7.7.5.2, THE |
| | ENCLOSURE SHALL BE SEPARATED FROM THE |
| | DUCT BY A MINIMUM OF 6" & A MAXIMUM OF |
| | 12".THE ENCLOSURE SHALL SERVE A SINGLE |
| | GREASE DUCT.PLEASE REVISE DETAIL. |
| | |
| | 2.DUCTS ARE TO BE INSPECTED PRIOR TO |
| | BEING ENCLOSED. |
| | |
| | 3.PROVIDE DISTANCE TO COMBUSTIBLES. |
| | |
| | 4.EXHAUST TO TERMINATE A MINIMUM OF |
| | 40" ABOVE THE ROOF SURFACE. NFPA 96 |
| | 7.8.2.1 (8). |
| | |
| | 5.10 FT MINIMUM REQUIRED FROM FRESH |
| | AIR INTAKE, PROPERTY LINES AND ADJACENT |
| | BUILDINGS. |
| | |
| | 6.PROVIDE MANUFACTURER SUBMITTAL DATA |
| | FOR THE HOOD. |
| | |
| | 7.EQUIPMENT SCHEDULE ON PLAN SHEET |
| | A3.6 ONLY INDICATES TWO EXHAUST FANS. |
| | PLANS INDICATE SIX NEW GRILL AREAS. |
| | PLEASE SPECIFY ALL NEW GREASE DUCT & |
| | HOODS WILL BE INSTALLED. |
| | |
| | 8.MINIMUM SLOPE OF 1/4" PER FOOT |
| | REQUIRED PER 2001 FBC(M) 506.3.9. |
| | |