Plan Review Notes
Plan Review Notes For Permit 04080588
Permit Number 04080588
Review Stop E
Sequence Number 1
Notes
Date Text
2004-08-24 00:00:00*********** UNSAT ***********
  
 1)NOTE: PLEASE CLARIFY CONTROL(S) FOR
 HIBACHI TABLE"S EXHAUST FANS?
  
 2)NOTE: PLEASE PROVIDE MORE INFORMATION
 FOR SHUT DOWN OF HOOD/ELECTRICAL DEVICES
 ETC.
 PER NFPA-96 CHAPTES 5,6,7,9
  
 3)NOTE: PLEASE SEE A NOTE ON PLANS MENT-
 -IONS ALL FLOOR RECEPTS TO BE CAPPED
 AND CIRCUITING ABANDONED.
 PLEASE SEE IF THESE FLOOR BOXES WILL NOT
 REMAIN ACCESSIBLE THEN WIRING WILL BE
 REQUIRED TO BE REMOVED COMPLETELY.
 RACEWAYS MAY REMAIN/ALONG W/ BOXES AFTER
 WIRING IS REMOVED.
  
 4)NOTE: PLEASE SEE SOME SHEETS ALONG
 W/ TITLE SHEETS CONTAIN "METRO DESIGN
 GROUP" PLEASE EITHER REMOVE THIS OR
 PLEASE INCLUDE REQUIRED LICENSE # INFOR-
 -MATION AS REQUIRED UNDER FS 471.023 AND
 FAC 61G15-23.002.
 PLEASE SEE ONE SET OF PLANS HAVE SAID
 SHEETS REMOVED AND RETAINED FOR FILE.
  
 THIS IS FOR ALL SHEETS WHEATHER OR NOT
 COMMENT IS MADE FROM OTHER REVIEWERS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SEE ANY COMMENTS FROM OTHER
 REVIEWS AS THEY MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]