| Date |
Text |
| 2004-08-25 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04080588 |
| | ADD: 700 S ROSEMARY # 208 |
| | CONT: SCHIPPA CONST |
| | TEL: (954)658-7493 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2)FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | PLANS ARE CONCEPTUAL IN NATURE, THEY DO |
| | NOT PROVIDE DETAILS AAS TO WHAT WORK |
| | WILL BE COMPLETED UNDER THIS PERMIT? |
| | |
| | 3) PLANS DO NOT PROVIDE THE MINIMUM |
| | BUILDING TYPE? |
| | |
| | 4) PLANS INDICATE A DOOR# 3, WITH WIND |
| | PRESSURES, IS THIS A NEW DOOR? IF THIS |
| | IS A NEW DOOR PROVIDE PRODUCT APPROVAL, |
| | FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: DOOR# 3. |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 5) PROVIDE INFORMATION ON THE LIVE FLOOR |
| | LOADS FOR THE RAISED SEATING AREA, ALSO |
| | PROVIDE THE DESIGN CRITERIA LIVE LOAD |
| | FOR THE RAMP, SEE TABLE 1604.1. |
| | |
| | 6) SEE 403.2.4.1. PERMANENT PLATFORMS |
| | THAT ARE GREATER THAN 3000 SQ FT FOR |
| | TYPE I, II,III AND IV CONSTRUCTION SHALL |
| | BE CONSTRUCTED OF MATERIALS AS REQUIRED |
| | FOR THE TYPE OF CONSTRUCTION OF THE |
| | BUILDING IN WHICH THE PERMANENT PLATFORM |
| | IS LOCATED.WHEN THE SPACE BENEATH THE |
| | PERMANENT PLATFORM IS USED FOR STORAGE |
| | OR ANY OTHER EQUIPMENT, WIRING, OR PLUMB |
| | ING, THE FLOOR CONSTRUCTION SHALL NOT BE |
| | LESS THAN 1-HOUR FIRE RESISTANT CON- |
| | STRUCTION. |
| | |
| | 7)704.2.1.4 CORRIDOR PARTITIONS, SMOKE |
| | STOP PARTITIONS, HORIZONTAL EXIT PART- |
| | ITIONS, EXIT ENCLOSURES, AND FIRE |
| | RATED WALLS REQUIRED TO HAVE PROTECTED |
| | OPENINGS SHALL BE EFFECTIVELY AND |
| | PERMANETLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE |
| | AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| | TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| | CEILING CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| | PROTECT ALL OPENINGS". |
| | |
| | 8) TABLE 803.3 MINIMUM INTERIOR FINISH |
| | CLASSIFICATION; PROVIDE INFORMATION |
| | BASED ON INTERIOR FINISH REQUIREMENTS |
| | BASED ON OCCUPANCY |
| | |
| | 9) PROVIDE A ROOM FINISH SCHEDULE. |
| | |
| | 10) 1204.2 SURROUNDING MATERIALS; |
| | THE WALLS & FLOORS OF ALL PUBLIC REST- |
| | ROOMS SHALL BE LINED WITH NONABSORBANT |
| | MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE |
| | FLOOR. |
| | |
| | 11) MISSING EXIT LIGHT AT THE REAR EXIT. |
| | |
| | 12) DOOR# 3, SHALL COMPLY WITH: |
| | 11-4.13.6 MANEUVERING CLEARENCES |
| | AT DOORS. MINIMUM MANEUVERING CLEARENCES |
| | AT DOORS THAT ARE NOT AUTOMATIC OR |
| | POWER-ASSISTED SHALL BE AS SHOWN IN |
| | FIG. 25. THE FLOOR OR GROUND AREA WITH |
| | IN THE REQUIRED CLEARENCES SHALL BE |
| | CLEAR & LEVEL. |
| | |
| | 13) PLANS INDIATE THE USE OF A STAIARWAY |
| | WITH 4 RISERS, TO COMPLY WITH: |
| | A)1007.5.1 STAIRS WITH A MINIMUM OF |
| | 4 RISERS SHALL BE EQUIPPED WITH HAND- |
| | RAILS LOCATED NO LESS THAN 34" NOR MORE |
| | THAN 38" ABOVE THE LEADING EDGE OF A |
| | TREAD. |
| | B) 1007.5.2 STAIRWAYS SHALL HAVE HAND- |
| | RAILS ON EACH SIDE. |
| | C) 1007.5.5. HANDRAILS SHALL EXTEND AT |
| | LEAST 12 INCHES HORIZONTALLY BEYOND THE |
| | TOP RISER OF A FLIGHT. .AT THE BOTTOM, |
| | THE HANDRAIL SHALL CONTINUE TO SLOPE FOR |
| | A DISTANCE OF THE DEPTH OF ONE TREAD |
| | FROM THE BOTTOM RISER. |
| | |
| | BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |