Plan Review Notes
Plan Review Notes For Permit 04080588
Permit Number 04080588
Review Stop B
Sequence Number 1
Notes
Date Text
2004-08-25 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04080588
 ADD: 700 S ROSEMARY # 208
 CONT: SCHIPPA CONST
 TEL: (954)658-7493
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PLANS ARE CONCEPTUAL IN NATURE, THEY DO
 NOT PROVIDE DETAILS AAS TO WHAT WORK
 WILL BE COMPLETED UNDER THIS PERMIT?
  
 3) PLANS DO NOT PROVIDE THE MINIMUM
 BUILDING TYPE?
  
 4) PLANS INDICATE A DOOR# 3, WITH WIND
 PRESSURES, IS THIS A NEW DOOR? IF THIS
 IS A NEW DOOR PROVIDE PRODUCT APPROVAL,
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS: DOOR# 3.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5) PROVIDE INFORMATION ON THE LIVE FLOOR
 LOADS FOR THE RAISED SEATING AREA, ALSO
 PROVIDE THE DESIGN CRITERIA LIVE LOAD
 FOR THE RAMP, SEE TABLE 1604.1.
  
 6) SEE 403.2.4.1. PERMANENT PLATFORMS
 THAT ARE GREATER THAN 3000 SQ FT FOR
 TYPE I, II,III AND IV CONSTRUCTION SHALL
 BE CONSTRUCTED OF MATERIALS AS REQUIRED
 FOR THE TYPE OF CONSTRUCTION OF THE
 BUILDING IN WHICH THE PERMANENT PLATFORM
 IS LOCATED.WHEN THE SPACE BENEATH THE
 PERMANENT PLATFORM IS USED FOR STORAGE
 OR ANY OTHER EQUIPMENT, WIRING, OR PLUMB
 ING, THE FLOOR CONSTRUCTION SHALL NOT BE
 LESS THAN 1-HOUR FIRE RESISTANT CON-
 STRUCTION.
  
 7)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 8) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 9) PROVIDE A ROOM FINISH SCHEDULE.
  
 10) 1204.2 SURROUNDING MATERIALS;
 THE WALLS & FLOORS OF ALL PUBLIC REST-
 ROOMS SHALL BE LINED WITH NONABSORBANT
 MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE
 FLOOR.
  
 11) MISSING EXIT LIGHT AT THE REAR EXIT.
  
 12) DOOR# 3, SHALL COMPLY WITH:
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 13) PLANS INDIATE THE USE OF A STAIARWAY
 WITH 4 RISERS, TO COMPLY WITH:
 A)1007.5.1 STAIRS WITH A MINIMUM OF
 4 RISERS SHALL BE EQUIPPED WITH HAND-
 RAILS LOCATED NO LESS THAN 34" NOR MORE
 THAN 38" ABOVE THE LEADING EDGE OF A
 TREAD.
 B) 1007.5.2 STAIRWAYS SHALL HAVE HAND-
 RAILS ON EACH SIDE.
 C) 1007.5.5. HANDRAILS SHALL EXTEND AT
 LEAST 12 INCHES HORIZONTALLY BEYOND THE
 TOP RISER OF A FLIGHT. .AT THE BOTTOM,
 THE HANDRAIL SHALL CONTINUE TO SLOPE FOR
 A DISTANCE OF THE DEPTH OF ONE TREAD
 FROM THE BOTTOM RISER.
  
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved