Text |
| 2004-08-21 00:00:00 | DENIED | | | REFERENCE: FBC-2001 FUEL GAS | | | FBC-2001 CHAPTER 1 | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2001 | | | FUEL GAS CODE. NOT ALL CUT SECTIONS SHOW | | | THE LENGTH. | | | 2. TYPE OF GAS, (LP OR NATURAL) | | | 3. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2001 FUEL GAS CODE SECS. 401.8 | | | THRU 402.5.2 AND TABLES 402(1) THRU | | | 402(34).TOTAL BTU LOAD OF EACH SYSTEM | | | IS NOT SHOWN. | | | 4. SUBMIT CALCULATIONS FOR COMBUSTION | | | AIR (IF APPLICABLE) PER FBC-2001 FUEL | | | GAS CODE SECTION 304. | | | 5. INDICATE HOW THE FUTURE GAS PIPING | | | WILL BE VALVED AND CAPPED OFF UNTILL THE | | | PIPING IS FINISHED. SECTION 104.2.1 | | | 6) ALL DRAWINGS SHALL BEAR THE NAME AND | | | SIGNATURE OF THE PERSON RESPONSIBLE FOR | | | THE DESIGN. SECTION 104.2.1 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|