Plan Review Notes
Plan Review Notes For Permit 04080570
Permit Number 04080570
Review Stop P
Sequence Number 1
Notes
Date Text
2004-08-21 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE. NOT ALL CUT SECTIONS SHOW
 THE LENGTH.
 2. TYPE OF GAS, (LP OR NATURAL)
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).TOTAL BTU LOAD OF EACH SYSTEM
 IS NOT SHOWN.
 4. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 5. INDICATE HOW THE FUTURE GAS PIPING
 WILL BE VALVED AND CAPPED OFF UNTILL THE
 PIPING IS FINISHED. SECTION 104.2.1
 6) ALL DRAWINGS SHALL BEAR THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 THE DESIGN. SECTION 104.2.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]