Plan Review Notes
Plan Review Notes For Permit 04080563
Permit Number 04080563
Review Stop E
Sequence Number 4
Notes
Date Text
2005-04-12 00:00:00RISER DIAGRAM SHOWS A 200 AMP SERVICE
  
 LOAD CALCULATION SHOWS 380 AMPS.RISER
  
 SHOW JUST TWO 200 AMP PANELS, BUT PLAN
  
 SHOWS TWO ADDITIONAL 60 AMP SUB PANELS.
  
 IN THE MASTER BEDROOM THERE APEARS TO BE
  
  
 TWO WALK IN CLOSETS, BOTH HAVE LIGHTS
  
 THAT APEAR TO BE IN VIOLATION OF 410.8
  
 A-D.PLAN SHOW A 100 AMP SERVICE ON
  
 DRAWINGS?PLANS SHOW TWO DIFFERENT
  
 LOCATIONS FOR THE A/C COMPRESSORS.
  
 PANEL SCHEDULES AND LOAD CALCULATIONS
  
 DO NOT REFLECT THE TWO 60 AMP
  
 SUB-PANELS.
  
 PLANS OUT FRONT UNDER "S"JL