 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW PRIOR TO ROUGH ELECTRICAL
 INSPECTION.
  
 1} SUBMIT RISER DIAGRAM REFLECTING ALL
 COMPONENTS IN THE SYSTEM. PLEASE
 CORRELATE RATINGS ON THE RISER WITH THE
 RATINGS SHOWN ON THE PLAN AT PANEL
 LOCATIONS, SEE REDLINED SET OF
 DRAWINGS.
  
 2} THE PANEL LOCATED IN THE "STORAGE
 ROOM" IS IN VIOLATION OF 240.24(D).
 ALSO
 NOTE THIS IS SHOWN AS 125 AMPS AND THE
 ORIGINAL RISER DID NOT SHOW ANY PANEL
 THAT SIZE.
  
 3} NOTE MISSING RECEPTACLES IN ALL
 BEDROOMS. 210.52(A)(1) & (2).
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
  