| 2004-12-07 00:00:00 | | | | ~~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW PRIOR TO ROUGH ELECTRICAL | | | INSPECTION. | | | | | | 1} SUBMIT RISER DIAGRAM REFLECTING ALL | | | COMPONENTS IN THE SYSTEM. PLEASE | | | CORRELATE RATINGS ON THE RISER WITH THE | | | RATINGS SHOWN ON THE PLAN AT PANEL | | | LOCATIONS, SEE REDLINED SET OF | | | DRAWINGS. | | | | | | 2} THE PANEL LOCATED IN THE "STORAGE | | | ROOM" IS IN VIOLATION OF 240.24(D). | | | ALSO | | | NOTE THIS IS SHOWN AS 125 AMPS AND THE | | | ORIGINAL RISER DID NOT SHOW ANY PANEL | | | THAT SIZE. | | | | | | 3} NOTE MISSING RECEPTACLES IN ALL | | | BEDROOMS. 210.52(A)(1) & (2). | | | | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|