| Plan Review Notes For Permit 04080563 |
| Permit Number |
04080563 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-11-17 00:00:00 | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW | | | | | | | | | | | | 1} PLEASE PROVIDE A CALCULATION INCLUDI- | | | NG ALL ADDED LOADS IMPOSED,ALL EXISTING | | | LOADS AND THE EXISTING OR PROPOSED SERVI | | | CE SPECIFICATIONS PER 215.15. INDICATE | | | IF THE SERVICE IS NEW OR EXISTING. | | | | | | 2}PLEASE PROVIDE PANEL SCHEDULES FOR | | | ALL PANELS | | | | | | 3} SHEET E-14 SHOWS 5 CONDENSING UNITS. | | | PLEASE VERIFY, CORRELATE LOCATION WITH | | | MECHANICAL PLAN AND SHOW CORRECT NUMBER | | | AND LOCATION ON ELECTRICAL PLAN. | | | | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|