| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} PLEASE PROVIDE A CALCULATION |
| | INCLUDING ALL ADDED LOADS IMPOSED,ALL |
| | EXISTING LOADS AND THE EXISTING OR |
| | PROPOSED |
| | SERVICE SPECIFICATIONS PER 215.15. |
| | ALSO INCLUDE PANEL SCHEDULES SO THAT |
| | BRANCH CIRCUIT REQUIREMENTS FOR OCP AND |
| | WIRE SIZES MAY BE REVIEWED. |
| | |
| | 2} PLEASE COMBINE EXISTING DEVICES AND |
| | ADDED DEVICES ON THE SAME DRAWING WITH |
| | EXISTING DEVICES IDENTIFIED. IT IS |
| | UNCLEAR LOOKING AT EXISTING AND |
| | PROPOSED PLANS WHICH WILL BE REMOVED |
| | DUE TO CHANGES IN ARCHITECTURE. COMBINE |
| | ALL DEVICES ON PROPOSED PLAN. |
| | |
| | 3} ONE OF THE EXISTING CONDENSING UNITS |
| | DOES NOT APPEAR ON THE NEW PLAN. THE |
| | ELECTRICAL PLAN DIFFERS FROM THE |
| | MECHANICAL PLAN, PLEASE CORRELATE. |
| | |
| | 4} PLEASE SEE MISSING RECEPT REQ'D |
| | FOR A/C EQUIPMENT. 210.63 |
| | |
| | 5} SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | |
| | 6} PLEASE SEE MISSING RECEPTS FOR |
| | FRONT AND/OR REAR OF DWELLING. |
| | 210.52(E). |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |
| | [email protected] |
| | FAX/:561/659-8026 |