 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE PROVIDE A CALCULATION
 INCLUDING ALL ADDED LOADS IMPOSED,ALL
 EXISTING LOADS AND THE EXISTING OR
 PROPOSED
 SERVICE SPECIFICATIONS PER 215.15.
 ALSO INCLUDE PANEL SCHEDULES SO THAT
 BRANCH CIRCUIT REQUIREMENTS FOR OCP AND
 WIRE SIZES MAY BE REVIEWED.
  
 2} PLEASE COMBINE EXISTING DEVICES AND
 ADDED DEVICES ON THE SAME DRAWING WITH
 EXISTING DEVICES IDENTIFIED. IT IS
 UNCLEAR LOOKING AT EXISTING AND
 PROPOSED PLANS WHICH WILL BE REMOVED
 DUE TO CHANGES IN ARCHITECTURE. COMBINE
 ALL DEVICES ON PROPOSED PLAN.
  
 3} ONE OF THE EXISTING CONDENSING UNITS
 DOES NOT APPEAR ON THE NEW PLAN. THE
 ELECTRICAL PLAN DIFFERS FROM THE
 MECHANICAL PLAN, PLEASE CORRELATE.
  
 4} PLEASE SEE MISSING RECEPT REQ'D
 FOR A/C EQUIPMENT. 210.63
  
 5} SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
  
 6} PLEASE SEE MISSING RECEPTS FOR
 FRONT AND/OR REAR OF DWELLING.
 210.52(E).
  